F200 Type B for smooth DC residual currents and operational safety, AC/DC sensitive, 10 ms short-time delayed, surge current resistant 3 kA (5 kA selective version), residual current circuit breakers (RCCBs) offer personal and material protection as well as protection against electrically ignited fires in accordance with DIN0100-410 and DIN0100-530. The residual current circuit breakers of the F200 B series ensure protection against sinusoidal alternating currents, pulsating currents and smooth DC residual currents to earth. As well as fault protection (protection against indirect contact), additional protection (with I n 30 mA) and fire protection (with I n 300 mA). They meet the product standards for type A IEC/EN 61008-1, 61008-2-1, 61543 (VDE 0664 10, 11, 30) and type B DIN EN 62423 (VDE 0664-40). Areas of application are in household, commercial or industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. The RCCB type B is suitable for non-linear circuits that can generate fault currents with smooth DC fault currents and with a wide variety of (high/) frequencies. These components are found in electronic equipment such as frequency converters. The RCCB type B has a frequency range of 0...2 kHz for detecting the fault current and offers high system availability.
Property | Value |
Rated voltage: | 230 V |
Rated current: | 40 A |
Mounting type: | DIN rail |
Protection class (IP): | IP20 |
Frequency: | 50/60 Hz |
Number of poles: | 2 |
Width in pitch units: | 2 |
Selective type: | no |
Residual current type: | B |
Additional equipment possible: | yes |
Installation depth: | 69 mm |
Short-time delayed type: | no |
Rated insulation voltage Ui: | 440 V |
Rated impulse withstand voltage Uimp: | 4 kV |
With locking device: | no |
Ambient temperature during operation: | -25 to 70 °C |
Pollution degree: | 3 |
Connectable conductor cross-section, single-wire: | 1 to 25 mm² |