Residual current circuit breakers (RCBOs) offer protection for people and property, as well as protection against electrically ignited fires in accordance with DIN0100-410 and DIN0100-530. They guarantee protection of single-phase circuits against overload and short-circuit currents, protection against sinusoidal, alternating currents and pulsating currents with a smooth DC residual current component of up to 6 mA to earth. As well as fault protection (protection against indirect contact), additional protection and fire protection. Areas of application are mainly in commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. The DS201 MA 110V series has no approval and is specifically designed for 110 V AC to 230 V AC applications. They meet the product standards IEC 61009-1, IEC 61009-2-1., The approvals are: CCC (CN), ABS (USA), DNV (DE), RINA (IT), RMRS (RU), Lloyds Register (GB)., Rated switching capacity according to IEC/EN 61009 Icn = 10 kA., RCBO DS201 MA 110V Type A is 1-pole protected (LS), 2-pole switching.
Property | Value |
Tripping characteristic: | B |
Current: | 15 A |
Fault current: | 0.03 A |
Voltage: | 240 V |
Frequency: | 50/60 Hz |
Number of poles: | 2 |
TE: | 2 |
Fault current type: | A |
Installation depth: | 35 mm |
Rated breaking capacity according to IEC 60947-2: | 15 kA |
Degree of protection (IP): | IP2X |
Energy limitation class: | 3 |
Overvoltage category: | 3 |
Pollution degree: | 2 |
Switching neutral conductor: | yes |
Number of protected poles: | 1 |
Flush-mounted installation: | no |
Type of voltage: | AC |
False tripping protection: | no |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Rated breaking capacity according to EN 61009: | 10 kA |
Rated breaking capacity Icn according to EN 61009-1: | 10 kA |
Breaking characteristic: | instantaneous |
With locking device: | no |
Connectable conductor cross-section, single-wire: | 0.75 to 25 mm² |
Connectable conductor cross-section, stranded: | 0.75 to 16 mm² |