Three-phase meter for measuring a three-wire or four-wire three-phase network via a direct connection up to a maximum of 80 A. The following values are output on a white backlit display with up to 7 digits: active energy (class 1), power, currents, voltages (LL, LN) and frequency, both per phase and total. Communication can take place via the integrated RS485 interface (Modbus RTU) or via the infrared interface for connecting a KNX module. The energy meter has one output. This can be used either as a pulse output to output the active energy or as an alarm output. Up to 25 alarm values (threshold values with time delay) can be set here. The meter is calibrated according to MID and approved according to IEC. The installation width is 7 DIN modules.
Property | Value |
Width in division units: | 7 |
Calibrated: | yes |
Pole type: | four-wire |
Meter type: | electronic |
Display type: | digital |
Mounting type: | REG |
Accuracy class: | B |
Protection class (NEMA): | other |
Maximum current (Imax): | 80 A |
Nominal voltage (Un) NL: | 57.7 to 288 V |
Pulse rate: | 1 to 999999 Imp/kWh (kvarh) |
Protection class (IP): | IP20 |
Frequency: | 50 to 60 Hz |
Tariff version: | Single tariff |
Energy type: | Active power |
Nominal current (In): | 5 A |
Version: | Direct measurement |
Measurement type load profile: | no |
EDL40 signature: | no |
With lock code: | no |
Pulse type: | S0 |
Nominal voltage (Un) LL: | 100 to 500 V |
Number of digits: | 7 |
Suitable for: | Reference |
Backstop: | yes |
Approval: | Measuring Instruments Directive |
Pulse output: | electrical |
Interface design: | Modbus |