The FI block (RCU) is for customer-side assembly with automatic circuit breakers from the S200 series. The resulting FI/LS combinations (RCBOs) offer personal and material protection as well as protection against electrically ignited fires in accordance with DIN0100-410 and DIN0100-530. They guarantee protection of 1P+N or 2P circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up to 6 mA to earth. As well as fault protection (protection against indirect contact), additional protection and fire protection. They meet the product standard IEC 61009 Appendix G, IEC 61009-2-1. Areas of application are commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. The special version is available for 400 V in the version with two poles for two-phase industrial applications where the voltage between the phases is 195 - 400 V AC.
Property | Value |
Nominal voltage: | 230 V |
Delay time adjustable: | no |
Rated residual current adjustable: | no |
Nominal current: | 63 A |
Residual current type: | A |
Number of poles: | 2 |
Rated residual current: | 0.03 A |
Frequency: | 50/60 Hz |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Connectable conductor cross-section, single-wire: | 25 mm² |
Connectable conductor cross-section, stranded: | 25 mm² |
False tripping protection: | no |
With locking device: | yes |
Protection class (IP): | IP2X |
Ambient temperature during operation: | -25 to 55 °C |