Residual current circuit breakers (RCCBs) offer protection for people and property as well as protection against electrically ignited fires in accordance with DIN0100-410 and DIN0100-530. The residual current circuit breakers of the F200 series ensure protection against sinusoidal alternating currents and pulsating currents against earth. As well as fault protection (protection against indirect contact), additional protection (with I n 30 mA) and fire protection (with I n 300 mA). They meet the product standards IEC 61008-1, IEC 61008-2-1. Approvals: CCC and UL 1053. These numerous approvals make the F200 A 110V fit for worldwide use. Areas of application are mainly in commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. F200 A 110V series specifically designed for 110 V AC and 230 V AC applications, due to the minimum test button voltage of 95 V AC.
Property | Value |
Rated voltage: | 400 V |
Rated current: | 40 A |
Rated residual current: | 30 mA |
Mounting type: | DIN rail |
Protection class (IP): | IP2X |
Frequency: | 50/60 Hz |
Number of poles: | 4 |
Width in pitch units: | 4 |
Selective type: | no |
Residual current type: | A |
Additional equipment possible: | yes |
Installation depth: | 69 mm |
Short-circuit strength (Icw): | 1 kA |
Surge current strength: | 0.25 kA |
Short-time delayed type: | no |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
With locking device: | yes |
Ambient temperature during Operating: | -25 to 55 °C |
Pollution level: | 2 |
Connectable conductor cross-section, stranded: | 0 to 25 mm² |
Connectable conductor cross-section, single-wire: | 25 mm² |