Residual current circuit breakers (RCCBs) offer personal and material protection as well as protection against electrically ignited fires in accordance with DIN0100-410 and DIN0100-530. The residual current circuit breakers of the F200 series ensure protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up to 6 mA to earth. As well as fault protection (protection against indirect contact), additional protection (with I n 30 mA) and fire protection (with I n 300 mA). They meet the product standards IEC/EN 61008-1, 61008-2-1, 61543 (VDE 0664 10, 11, 30) and for F200 A to 100 A UL 1053. Areas of application are household, commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. Numerous approvals make the F200 fit for worldwide use.
Property | Value |
Rated voltage: | 400 V |
Rated current: | 40 A |
Rated residual current: | 30 mA |
Mounting type: | DIN rail |
Protection class (IP): | IP2X |
Frequency: | 50/60 Hz |
Number of poles: | 4 |
Width in Division units: | 4 |
Selective type: | no |
Residual current type: | A |
Additional equipment possible: | yes |
Installation depth: | 69 mm |
Short-circuit strength (Icw): | 1 kA |
Surge current strength: | 0.25 kA |
Short-time delayed type: | no |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
With Locking device: | yes |
Ambient temperature during operation: | -25 to 55 °C |
Pollution level: | 2 |
Connectable conductor cross-section, stranded: | 0 to 25 mm² |
Connectable conductor cross-section, solid: | 25 mm² |