Description
Features
Reviews
Motor protection switch MS116 with thermal and electromagnetic protection represents the compact and economical series for motor protection up to 15 kW (400 V) with a module width of 45 mm. The temperature-compensated device has a rotary handle operation with a clear switch position indicator I/0. The rotary handle can be locked in the 0 position using a locking device. Auxiliary and signal contacts as well as undervoltage and shunt current releases can be installed without tools. 3-phase rails for 65 A or 100 A and feed blocks for 25 mm² or 35 mm² allow several motor protection switches to be fed together. Protective housings and accessories for control cabinet and door installation complete the range.
Property | Value |
Number of poles: | 3 |
Rated operating voltage: | 690 V |
Rated operating power at AC-3, 400 V: | 0.06 kW |
Rated continuous current Iu: | 0.25 A |
Rated ultimate short-circuit breaking current Icu at 400 V, AC: | 100 kA |
Overload release current setting: | 0.16 to 0.25 A |
Tripping technology: | thermomagnetic |
Phase failure sensitive: | yes |
Main circuit connection type: | screw connection |
Device design: | Complete device in housing |
Protection class (IP): | IP20 |
Width: | 45 mm |
Setting range of the instantaneous short-circuit release: | 3.1 A |
With integrated auxiliary switch: | no |
With integrated undervoltage release: | no |
Height: | 90 mm |
Depth: | 85.6 mm |
Design of the operating element: | Rotary knob |
With thermal protection: | yes |
Features
HAN
1SAM250000R1002
Manufacturer
HAB
MS116-0.25
GTIN
4013614320255
Triggering technology
Thermomagnetic
Rated operational power at AC-3, 400 V
0.06kW
Rated operating voltage
690V
Rated continuous current Iu
0.25A
Rated ultimate short-circuit breaking current Icu at 400 V, AC
100kA
Width
45 mm
Setting range of the instantaneous short-circuit release
3.1 A
Connection type main circuit
Screw connection
Device type
Complete device in housing
Height
90 mm
With integrated auxiliary switch
No
With integrated undervoltage release
No
With thermal protection
Yes
Sensitive to phase failure
Yes
Number of poles
3
IP protection)
IP20
Depth
85.6 mm
Overload release current setting
0.16 to 0.25A
Design of the actuating element
Rotary knob
No reviews yet — your comment may be first.
All reviews 0