Description
Features
Reviews
Combined surge protection, tested in category D, C, B (EN 61643), suitable for twisted pair cables for signal transmission. For protecting resistance-sensitive systems with frequencies between 120kHz and 160kHz. Suitable for direct current applications up to a maximum of 4 A. Available for nominal voltages of 6, 15, 30, 50 and 110 volts. For use at limits from LPZ 0 for protection against flashover (typically at the point of cable entry) up to LPZ 3 to protect sensitive electronic equipment.
Property | Value |
Signaling on the device: | optical |
Mounting type: | other |
Nominal discharge current (8/20): | 10 kA |
Nominal load current: | 4 A |
Maximum continuous voltage DC: | 36.7 V |
Maximum continuous voltage AC: | 25 V |
Protection level wire/wire: | 46 V |
Protection level wire/earth: | 46 V |
Protection level Signal ground/protective ground: | 46 V |
Protection level wire/signal ground: | 46 V |
With remote signaling contact: | yes |
Explosion-tested version: | no |
Arrester monitoring: | no |
Nominal voltage DC: | 30 V |
Frequency: | 0.13 MHz |
Limit frequency: | 0.13 MHz |
Nominal voltage AC: | 25 to 36.7 V |
Lightning impulse current (10/350 µs): | 2.5 kA |
Features
Explosion-tested version
No
Lightning surge current (10/350 µs)
2.5 kA
With remote signaling contact
Yes
Highest continuous voltage DC
36.7 V
Nominal load current
4 A
Nominal voltage DC
30 V
Protection level wire/wire
46 V
Protection level wire/earth
46 V
Limit frequency
0.13 MHz
HAB
OVR30H
Minimal order
10 pieces
Manufacturer
HAN
7TCA085400R0358
GTIN
5415022375480
Frequency
0.13MHz
Highest continuous voltage AC
25V
Mounting type
Other
Nominal discharge current (8/20)
10kA
Nominal voltage AC
25 to 36.7 V
Signaling on the device
Optical