The circuit breakers of the S 200 U DC series protect cables and lines against overload and short circuits in accordance with DIN0100-430 and DIN0100-530. They comply with the construction regulations DIN0660-101 or IEC/EN60947-2 and UL489 or CSA 22.2 No. 5. For better visibility when wiring, the connection opening for cables is above the connection opening for the phase busbar. Conductor cross-sections of up to 25 mm² can be connected directly to the device via the connection terminal with insulation in protection class IP20. The combination of the approvals according to UL489, CSA 22.2 No. 5 and IEC/EN60947-2 make this device a device that can be used worldwide for high demands and is subjected to three intensive tests for quality and performance before delivery.
Property | Value |
Tripping characteristic: | Z |
Rated current: | 16 A |
Rated voltage: | 125 V |
Type of voltage: | DC |
Width in modular spacing: | 2 |
Number of poles (total): | 2 |
Energy limitation class: | 3 |
Additional equipment possible: | yes |
Overvoltage category: | 3 |
Installation depth: | 69 mm |
Protection class (IP): | IP20 |
Rated switching capacity Icn according to EN 60898 at 230 V: | 14 kA |
Rated switching capacity Icu according to IEC 60947-2 at 230 V: | 14 kA |
Pollution degree: | 2 |
Switching neutral conductor: | no |
Number of protected poles: | 2 |
Suitable for flush-mounted installation: | no |
Ambient temperature during operation: | -25 to 55 °C |
Connectable conductor cross-section, stranded: | 0 to 25 mm² |