The circuit breakers of the S 400 series protect cables and lines against overload and short circuits in accordance with DIN0100-430 and DIN0100-530. They comply with the construction regulations DIN0641-11 and IEC/EN 60898-1, DIN0660-101 and IEC/EN60947-2. Their patented connection terminal ensures simple and safe contacting and handling using a pressure plate. Conductor cross-sections of up to 35 mm² can be connected directly to the device via the connection terminal with insulation in protection class IP20. Contacting is made directly via the plug-in base system and the outer conductor contact can be freely selected (L1, L2 or L3). The extensive range of accessories offers you everything you need for your installation tasks. Numerous approvals make the S 400 fit for worldwide use. Each device is subjected to three intensive tests for quality and performance before delivery.
Property | Value |
Tripping characteristic: | B |
Rated current: | 6 A |
Rated voltage: | 400 V |
Type of voltage: | AC |
Frequency: | 50 to 60 Hz |
Width in pitch units: | 4 |
Number of poles (total): | 4 |
Energy limitation class: | 3 |
Additional equipment possible: | yes |
Overvoltage category: | 3 |
Installation depth: | 75 mm |
Protection class (IP): | IP20 |
Rated switching capacity Icn according to EN 60898 at 230 V: | 10 kA |
Rated switching capacity Icu according to IEC 60947-2 at 230 V: | 50 kA |
Rated switching capacity Icu according to IEC 60947-2 at 400 V: | 50 kA |
Rated switching capacity Icn according to EN 60898 at 400 V: | 10 kA |
Pollution level: | 3 |
Switching neutral conductor: | yes |
Number of protected poles: | 3 |
Suitable for flush-mounted installation: | no |
Rated insulation voltage Ui: | 440 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Ambient temperature during operation: | -25 to 55 °C |
Connectable conductor cross-section, single-wire: | 0.75 to 25 mm² |