The high-performance circuit breakers in the S800S series protect cables and lines against overload and short circuits. They have a rated short-circuit breaking capacity of 50 kA at 240/415 V AC. They can also be used for voltages up to 400/690 V AC and for direct voltages. With its thermal tripping mechanism, it offers equally effective protection against overloads, as does its electromechanical tripping mechanism against short circuits. The S800S complies with the IEC/EN 60947-2 standard and can be used for industrial purposes. Numerous approvals make it suitable for use worldwide and the extensive range of accessories makes it even more convenient to use. Thanks to the very fast arc extinguishing, your installation is optimally protected with the S800S.
Property | Value |
Tripping characteristic: | K |
Rated current: | 32 A |
Rated voltage: | 400 V |
Type of voltage: | AC |
Frequency: | 50 to 60 Hz |
Width in pitch units: | 3 |
Number of poles (total): | 2 |
Energy limitation class: | 3 |
Additional equipment possible: | yes |
Overvoltage category: | 3 |
Installation depth: | 82.5 mm |
Protection class (IP): | IP20 |
Rated switching capacity Icn according to EN 60898 at 230 V: | 25 kA |
Rated switching capacity Icu according to IEC 60947-2 at 230 V: | 50 kA |
Rated switching capacity Icu according to IEC 60947-2 at 400 V: | 50 kA |
Rated switching capacity Icn according to EN 60898 at 400 V: | 25 kA |
Pollution degree: | 3 |
Switching neutral conductor: | no |
Number of protected poles: | 2 |
Suitable for flush-mounted installation: | no |
Rated insulation voltage Ui: | 690 V |
Rated impulse withstand voltage Uimp: | 8 kV |
Ambient temperature during operation: | -25 to 60 °C |
Connectable conductor cross-section, stranded: | 0 to 70 mm² |
Connectable conductor cross-section, single-wire: | 0 to 50 mm² |