Description
Features
Reviews
High-performance circuit breaker to protect against overload and short circuit of cables and lines. Meets the requirements of UL489 and IEC 60947-2. Conductor cross-sections of up to 70 mm² can be connected directly to the device. Safe electrical isolation in accordance with IEC 60947-2. Auxiliary and signal switches can be attached to the device without additional wiring.
| Property | Value |
| Tripping characteristic: | Z |
| Rated current: | 50 A |
| Rated voltage: | 240 V |
| Type of voltage: | AC |
| Frequency: | 50 to 60 Hz |
| Width in pitch units: | 4 |
| Number of poles (total): | 4 |
| Energy limitation class: | 3 |
| Additional equipment possible: | yes |
| Overvoltage category: | 3 |
| Installation depth: | 82.5 mm |
| Protection class (IP): | IP20 |
| Rated switching capacity Icn according to EN 60898 at 230 V: | 40 kA |
| Rated switching capacity Icu according to IEC 60947-2 at 230 V: | 50 kA |
| Rated switching capacity Icu according to IEC 60947-2 at 400 V: | 50 kA |
| Rated switching capacity Icn according to EN 60898 at 400 V: | 40 kA |
| Pollution level: | 2 |
| Switching neutral conductor: | no |
| Number of protected poles: | 4 |
| Suitable for flush-mounted installation: | no |
| Rated insulation voltage Ui: | 690 V |
| Rated impulse withstand voltage Uimp: | 8 kV |
| Ambient temperature during operation: | -25 to 60 °C |
| Connectable conductor cross-section, stranded: | 0 to 70 mm² |
| Connectable conductor cross-section, single-wire: | 0 to 50 mm² |
Features
HAB
S804U-Z50
Manufacturer
HAN
2CCS864017R0505
GTIN
7612271214753
Connectable conductor cross-section solid
0 to 50 mm²
Connectable conductor cross-section stranded
0 to 70 mm²
Number of protected poles
4
Trigger characteristics
Z
Rated insulation voltage Ui
690V
Rated switching capacity Icn according to EN 60898 at 230 V
40kA
Rated switching capacity Icn according to EN 60898 at 400 V
40kA
Rated switching capacity Icu according to IEC 60947-2 at 230 V
50kA
Rated switching capacity Icu according to IEC 60947-2 at 400 V
50kA
Rated voltage
240V
Rated impulse withstand voltage Uimp
8kV
Rated current
50A
Width in pitch units
4
Installation depth
82.5 mm
Energy limitation class
3
Frequency
50 to 60 Hz
Suitable for flush-mounted installation
No
Switching neutral conductor
No
Number of poles (total)
4
IP protection)
IP20
Voltage type
AC
Ambient temperature during operation
-25 to 60 °C
Degree of contamination
2
Additional equipment possible
Yes
Overvoltage category
3
No reviews yet — your comment may be first.
All reviews 0