Description
Features
Reviews
ZP combined arrester compact design for NAR on 40mm SaS in snap-on technology type T1+T2+T3, without external lightning protection 7.5 kA, TT/TNS system 3PN, leakage current free
| Property | Value |
| Maximum continuous voltage AC: | 300 V |
| Lightning impulse current (10/350 µs): | 7.5 kA |
| Protection level: | 1.5 kV |
| Number of poles: | 4 |
| Nominal voltage AC: | 240 V |
| Size: | 2 TE |
| Remote signaling: | no |
| Signaling on the device: | optical |
| Network type TN-CS: | no |
| Network type DC: | no |
| Network type TN: | no |
| Energetically coordinated protection effect to the end device: | no |
| Mounting type: | Busbar |
| Protection level N-PE: | 1.2 kV |
| Network type TT: | yes |
| Integrated back-up fuse: | no |
| Max. conductor cross-section rigid (single/multi-wire): | 35 mm² |
| Max. Conductor cross-section flexible (fine-stranded): | 25 mm² |
| Network type other: | no |
| Protection level LN: | 0.442 kV |
| Network type TN-C: | no |
| Network type IT: | no |
| Network type TN-S: | yes |
| Protection class (IP): | IP20 |
Features
Max. conductor cross-section rigid (single/multi-wire)
35 mm²
Max. conductor cross-section flexible (fine-stranded)
25 mm²
Lightning surge current (10/350 µs)
7.5 kA
Protection level
1.5 kV
Network form TT
Yes
Network type TN-S
Yes
Network form TN
No
Network type TN-C
No
Network type TN-C-S
No
Protection level L-N
0.442 kV
Network type DC
No
Protection level N-PE
1.2 kV
Integrated backup fuse
No
Network type IT
No
HAB
ZP T1 T2 T3 7.5kA TT/TNS
Manufacturer
HAN
R9LC2707
GTIN
4015153826731
Size
2 HP
Highest continuous voltage AC
300V
Mounting type
Busbar
Nominal voltage AC
240V
Number of poles
4
IP protection)
IP20
Signaling on the device
Optical
No reviews yet — your comment may be first.
All reviews 0