consisting of: Mains-side connection compartment (NAR, top), H x W (mm): 300 x 250: With 40 mm busbars, 355 A, 5-pole (Cu 2 x 12 x 5 mm) and sealable cover with transparent cover and empty space for overvoltage protection, Mains-side separation point: NH00 fuse element, 3-pole, on 40 mm busbar (clamp terminal), Transformer compartment, H x W (mm): 450 x 250: With insulators, primary wiring 35 mm² on Cu connection lugs and sealable cover with transparent cover, For on-site standard transformer lug 170 mm long in accordance with Form A according to DIN0603-2-2, Hole spacing 130 mm, System-side connection compartment (AAR), with system-side separation point, H x W (mm): 450 x 250: Load disconnector 125A, 3-pole, on device mounting rail (box terminal up to 50mm²) and N+PE terminal block 50/35mm²
Property | Value |
Height: | 1205 mm |
Width: | 250 mm |
Depth: | 166.11 mm |
Number of division units per DIN rail: | 12 |
With N-PE terminals: | no |
With cover: | yes |
Type of cover: | closed |
With mounting plate: | no |