HVI cable (high-voltage-resistant insulated conductor) in a support tube, to maintain the separation distance from electrically conductive parts in accordance with DIN EN 62305-3 (VDE 0185-305-3) in order to prevent dangerous flashovers between parts of the external lightning protection and internal, conductive parts (electrical system, pipes, etc.). To prevent creeping discharges, the HVI cable is equipped with a special external sheath that enables high lightning impulse voltages to be diverted to a reference potential. HVI cable design (gray), with internal end closure and PA spring element in the support tube (length 3200 mm) with air-termination rod (D22 / 16 / 10 mm length 2500 mm), with a head piece, a PA connection element and an earth connection element. Equivalent separation distance s 75 cm (in air), s 150 cm (solid material).
| Property | Value |
| High-voltage-resistant insulated version: | yes |
| Conductor diameter: | 5 mm |
| Surface: | untreated |
| Number of individual wires: | 1 |
| Conductor class: | Class 1 = single wire |
| Max. tensile load: | 950 N |
| Max. equivalent separation distance s (in air): | 0.75 m |
| Insulation material: | Polyethylene (PE) |
| Use in hazardous areas: | yes |
| Conductor cross-section: | 19 mm² |
| Conductor material: | copper |
| Max. equivalent separation distance s (solid materials): | 1.5 m |
| Color: | gray |