Single-pole, coordinated N-PE lightning current arrester DEHNgap Maxi S, type 1 according to EN 6143-11. Total current arrester specially designed for use in the TT system in the 3+1 and 1+1 circuit according to DIN0100-534 between N and PE for mounting on industrial busbar systems, for protecting low-voltage consumer systems against overvoltages even in the event of direct lightning strikes, for use in the lightning protection zone concept at the interfaces 0A- 1 in the 3+1 circuit variant
| Property | Value |
| Lightning impulse current (10/350 µs): | 100 kA |
| Maximum continuous voltage AC: | 255 V |
| Nominal voltage AC: | 230 V |
| Protection level: | 2.5 kV |
| Follow current extinguishing capacity: | 0.1 kA |
| Mounting type: | Busbar |
| Signaling on the device: | with fiber optic |
| Test class type 1: | yes |
| Network type TT: | yes |
| Specific energy (W/R): | 2500 kJ/Ohm |
| Number of conductors (without earth): | 1 |
Features
Lightning surge current (10/350 µs)
100 kA
Protection level
2.5 kV
Number of conductors (excluding earth)
1
Network form TT
Yes
Manufacturer
HAN
900050
GTIN
4013364107496
Highest continuous voltage AC
255V
Mounting type
Busbar
Nominal voltage AC
230V
Signaling on the device
With fiber optic