Single-pole, coordinated DEHNsolid lightning current arrester, type 1 according to EN 61643-11 on a spark gap basis. Very high lightning current discharge capacity and low protection level. For protecting low-voltage consumer systems against overvoltages, even in the event of direct lightning strikes. For use in the lightning protection zone concept at the interfaces 0A - 1.
Property | Value |
Lightning impulse current (10/350 µs): | 200 kA |
Maximum continuous voltage AC: | 255 V |
Protection level: | 2.5 kV |
Follow current extinguishing capacity: | 3 kA |
Mounting type: | Busbar |
Test class type 1: | yes |
Network form TT: | yes |
Specific energy (W/R): | 10000 kJ/Ohm |
Network form TN-CS: | yes |
Network type TN-S: | yes |
Network type TN: | yes |
Network type TN-C: | yes |
Features
Lightning surge current (10/350 µs)
200 kA
Protection level
2.5 kV
Network form TT
Yes
Network type TN-S
Yes
Network form TN
Yes
Network type TN-C
Yes
Network type TN-C-S
Yes
Manufacturer
HAN
900230
GTIN
4013364153783
Highest continuous voltage AC
255V
Mounting type
Busbar