Tested combination arrester type 1+type 2+type 3 according to DIN EN 61643-11 for TN-S systems (4+0 circuit) including overcurrent-protected 230 V power supply (N and L) including replacement fuse for RfZ / APZ in accordance with VDE-AR-N 4100, can be installed completely without tools using Click+Power connection technology for the 40 mm busbar system and push-in earthing terminal, for use in the main power supply system according to DIN0100-443 in buildings with an external lightning protection system (lightning protection class III/IV). A suitable cover clip according to DIN0603-1 for every commercially available meter panel, plus 2 x socket and 2 x plug (without connection cables) for wiring the intelligent measuring system according to VDE-AR 4100 is included in the scope of delivery.
Property | Value |
Maximum continuous voltage AC: | 255 V |
Lightning impulse current (10/350 µs): | 50 kA |
Number of poles: | 4 |
Nominal voltage AC: | 230 V |
Signaling on the device: | optical |
Energetically coordinated protective effect for the end device: | yes |
Mounting type: | busbar |
Protection level N-PE: | 1.5 kV |
Network type TT: | no |
Specific energy (W/R): | 39.06 kJ/Ohm |
Follow current extinguishing capacity: | 25 kA |
Max. conductor cross-section rigid (single/multi-wire): | 25 mm² |
Network type TN-S: | yes |
Protection level L-PE: | 1.5 kV |
Protection class (IP): | IP30 |