Description
Features
Reviews
Single-pole, coordinated N-PE lightning current arrester DEHNgap Maxi, type 1 according to EN 61643-11. Total current arrester specially for use in the TT system in the 3+1 and 1+1 circuit according to DIN0100-534 between N and PE for Uc= 255V. For protecting low-voltage consumer systems against overvoltages, even in the event of direct lightning strikes. For use in the lightning protection zone concept at the interfaces 0A- 1 in the 3+1 circuit variant.
Property | Value |
Lightning impulse current (10/350 µs): | 100 kA |
Maximum continuous voltage AC: | 255 V |
Protection level: | 1.5 kV |
Follow current extinguishing capacity: | 0.1 kA |
Mounting type: | DIN rail TH35 |
Size: | 2 TE |
With remote signaling contact: | yes |
Signaling on the device: | optical |
Test class type 1: | yes |
Network type TT: | yes |
Specific energy (W/R): | 2500 kJ/Ohm |
Max. conductor cross-section rigid (single/multi-wire): | 50 mm² |
Max. conductor cross-section flexible (fine-stranded): | 35 mm² |
Number of conductors (without earth): | 1 |
Protection class (IP): | IP20 |
Features
Max. conductor cross-section rigid (single/multi-wire)
50 mm²
Max. conductor cross-section flexible (fine-stranded)
35 mm²
Lightning surge current (10/350 µs)
100 kA
Protection level
1.5 kV
With remote signaling contact
Yes
Number of conductors (excluding earth)
1
Network form TT
Yes
Manufacturer
HAN
961185
GTIN
4013364157330
Size
2 HP
Highest continuous voltage AC
255V
Mounting type
DIN rail TH35
IP protection)
IP20
Signaling on the device
Optical
No reviews yet — your comment may be first.