Description
Features
Reviews
Electronic trip unit for motor protection according to IEC60947-4-1 for basic device PKE12, electronic wide-range overload protection (4:1), phase failure and asymmetry protection, adjustable trip class. Interface for connection to SmartWire-DT. World market device, ATEX approval
Property | Value |
Starting value of the instantaneous short-circuit release setting range: | 4.65 A |
Ending value of the instantaneous short-circuit release setting range: | 18.6 A |
Rated continuous current Iu: | 1.2 A |
Overload release current setting: | 0.3 to 1.2 A |
Number of poles: | 3 |
Short-circuit release function: | delayed |
Voltage type for actuation: | self-supplied |
With Earth fault protection function: | no |
Motor protection design: | electronic release |
Features
End value of the undelayed short-circuit release setting range
18.6 A
Initial value of the undelayed short-circuit release setting range
4.65 A
HAB
PKE-XTUA-1,2 0.3-1.2A for PKE12
Manufacturer
HAN
121727
GTIN
4015081195374
Rated continuous current Iu
1.2A
Number of poles
3
Voltage type for actuation
Self-sufficient
Overload release current setting
0.3 to 1.2A
No reviews yet — your comment may be first.
All reviews 0