Power contactor, application: mini contactor for motors and resistive loads, DILEM power contactors, utilization category: AC-1: non-inductive or slightly inductive loads, resistance furnaces, AC-3: squirrel cage motors: starting, switching off during operation, AC-4: squirrel cage motors: starting, plugging, reversing, inching, connection technology: screw terminals, description: with auxiliary switch, poles: 3-pole, rated operating current AC-3 380 V 400 V: Ie= 12 A, rated operating current AC-1 conventional thermal current, 3-pole, 50 - 60 Hz open at 40 °C: Ith = Ie= 22 A, encapsulated: Ith= 16 A, rated operating current AC-1 conventional thermal current 1-pole open: Ith= 50 A, encapsulated: Ith= 40 A, max. Rated operating power of three-phase motors 50 - 60 Hz AC-3 220 V 230 V: P= 3 kW, 380 V 400 V: P= 5.5 kW, 660 V 690 V: P= 4 kW, max. Rated operating power of three-phase motors 50 - 60 Hz AC-4 220 V 230 V: P= 1.5 kW, 380 V 400 V: P= 3 kW, 660 V 690 V: P= 3 kW, can be used for: .DILEM, .DILE, contact configuration S = normally open: 1 S, current type AC/DC: direct current operation
Property | Value |
Number of normally open contacts as main contacts: | 3 |
Number of auxiliary contacts as normally open contacts: | 1 |
Rated operating power at AC-3, 400 V: | 5.5 kW |
Rated operating power at AC-4, 400 V: | 3 kW |
Rated operating current Ie at AC-1, 400 V: | 22 A |
Rated operating current Ie at AC-3, 400 V: | 12 A |
Rated operating current Ie at AC-4, 400 V: | 6.6 A |
Voltage type for actuation: | DC |
Rated control supply voltage Us at DC: | 24 V |
Connection type main circuit: | screw connection |
Suitable for series installation: | no |
Rated operating power NEMA: | 3.7 kW |