Complete range of compact residual current circuit breakers for a wide range of applications, for fault and additional protection, large number of available rated currents, extensive range of accessories, real contact position indicator, automatic reclosure possible, suitable for outdoor use (construction site power and outdoor distribution boards) down to -25°C
Property | Value |
Protection class (IP): | IP20 |
Voltage type: | AC |
Number of poles: | 4 |
Weight: | 0.37 |
Weight unit: | KG |
Mounting type: | DIN rail |
Installation depth: | 70.5 mm |
Rated current: | 63 A |
Rated voltage: | 240 V |
Rated insulation voltage Ui: | 440 V |
Rated residual current: | 0.1 A |
Residual current type: | other |
Short-circuit strength (Icw): | 10 kA |
Surge current strength: | 3 kA |
Pollution degree: | 2 |
Width in pitch units: | 4 |
Short-time delayed type: | yes |
Frequency: | 50/60 Hz |
Connectable conductor cross-section, solid: | 1.5 - 35 mm² |
Connectable conductor cross-section, stranded: | 1.5 - 16 mm² |
With locking device: | yes |
Ambient temperature during operation: | -25 - 40 °C |
Additional devices possible: | yes |
Rated impulse withstand voltage Uimp: | 4 kV |
RAL number (similar): | 7035 |
Brief description: | FI switch, 63A, 4p, 100mA, type G/F |
Features
HAB
FRCMM-63/4/01-G/F 63A 4p 100mA Type G
Manufacturer
HAN
187416
GTIN
4015081824748
Connectable conductor cross-section solid
1.5 - 35 mm²
Connectable conductor cross-section stranded
1.5 - 16 mm²
Rated residual current
0.1A
Rated insulation voltage Ui
440V
Rated voltage
240V
Rated impulse withstand voltage Uimp
4kV
Rated current
63 A
Width in pitch units
4
Installation depth
70.5 mm
Residual current type
Other
Frequency
50/60Hz
Weight
0,37
Weight unit
kg
Short description
Residual current switch, 63A, 4p, 100mA, type G/F
Short circuit strength (Icw)
10kA
Short-time delayed type
Yes
With locking device
Yes
Mounting type
DIN rail
Number of poles
4
RAL number (similar)
7035
IP protection)
IP20
Voltage type
AC
Surge current strength
3kA
Ambient temperature during operation
-25 - 40 °C
Degree of contamination
2
Additional equipment possible
Yes