Power contactor, Application: Power contactor for 4-pole consumers, Power contactors up to 200 A, 4-pole, Utilization category: AC-1: Non-inductive or slightly inductive load, resistance furnaces, AC-3: Squirrel cage motors: Starting, switching off during operation, Connection technology: Screw terminals, Poles: 4-pole, 380 V 400 V: Ie= 18 A, conventional thermal current, 3-pole, 50 - 60 Hz open at 40 °C: Ith = Ie= 32 A, encapsulated: Ith= 27 A, conventional thermal current 1-pole open: Ith= 84 A, encapsulated: Ith= 76 A, 220 V 230 V: P= 5 kW, 380 V 400 V: P= 7.5 kW, 660 V 690 V: P= 11 kW, Contacts S = Normally open: 1 S, Notes: Switching elements according to EN 50012., Integrated protective circuit in the control electronics., Current type AC/DC: Direct current operation
Property | Value |
Number of normally open contacts as main contacts: | 4 |
Number of auxiliary contacts as normally open contacts: | 1 |
Rated operating power at AC-3, 400 V: | 7.5 kW |
Rated operating power at AC-4, 400 V: | 7 kW |
Rated operating current Ie at AC-1, 400 V: | 32 A |
Rated operating current Ie at AC-3, 400 V: | 18 A |
Rated operating current Ie at AC-4, 400 V: | 15 A |
Voltage type for actuation: | DC |
Rated control supply voltage Us at DC: | 110 to 130 V |
Connection type main circuit: | Screw connection |
Suitable for series installation: | no |
Rated operating power NEMA: | 11 kW |