Description
Features
Reviews
Power contactor, Application: Power contactor for 4-pole consumers, Power contactors up to 200 A, 4-pole, Utilization category: AC-1: Non-inductive or slightly inductive load, resistance furnaces, AC-3: Squirrel cage motors: Starting, switching off during operation, Connection technology: Screw terminals, Poles: 4-pole, 380 V 400 V: Ie= 25 A, conventional thermal current, 3-pole, 50 - 60 Hz open at 40 °C: Ith = Ie= 45 A, encapsulated: Ith= 36 A, conventional thermal current 1-pole open: Ith= 117 A, encapsulated: Ith= 105 A, 220 V 230 V: P= 7.5 kW, 380 V 400 V: P= 11 kW, 660 V 690 V: P= 14 kW, Contacts S = Normally open: 1 S, Notes: Switching elements according to EN 50012., Current type AC/DC: Alternating current operation
Property | Value |
Number of normally open contacts as main contacts: | 4 |
Number of auxiliary contacts as normally open contacts: | 1 |
Rated operating power at AC-3, 400 V: | 11 kW |
Rated operating power at AC-4, 400 V: | 7 kW |
Rated operating current Ie at AC-1, 400 V: | 45 A |
Rated operating current Ie at AC-3, 400 V: | 25 A |
Rated operating current Ie at AC-4, 400 V: | 15 A |
Voltage type for actuation: | AC |
Rated control supply voltage Us at AC 50 Hz: | 230 V |
Rated control supply voltage Us at AC 60 Hz: | 240 V |
Connection type main circuit: | Screw connection |
Suitable for series installation: | no |
Rated operating power NEMA: | 11 kW |
Features
HAB
DILMP45-10 (230V50HZ,240V60HZ) 45A/AC1 4p
Manufacturer
HAN
109826
GTIN
4015081093960
Connection type main circuit
Screw connection
Number of auxiliary contacts as normally open
1
Number of normally open contacts as main contacts
4
Rated operating power NEMA
11kW
Rated operational power at AC-3, 400 V
11kW
Rated operational power at AC-4, 400 V
7kW
Rated operational current Ie at AC-1, 400 V
45A
Rated operational current Ie at AC-3, 400 V
25A
Rated operational current Ie at AC-4, 400 V
15A
Rated control supply voltage Us at AC 50 Hz
230V
Rated control supply voltage Us at AC 60 Hz
240V
Suitable for series installation
No
Voltage type for actuation
AC
No reviews yet — your comment may be first.
All reviews 0