Safety contactor, Application: Power contactor for motors, complete devices up to 170 A, Utilization category: AC-1: Non-inductive or slightly inductive load, resistance furnaces, AC-3: Squirrel cage motors: starting, switching off during operation, AC-4: Squirrel cage motors: starting, countercurrent braking, reversing, tapping, Connection technology: screw terminals, Note: Also suitable for motors of efficiency class IE3., IE3-capable devices are marked with the logo on the packaging., Description: Auxiliary switch module permanently connected to the basic device (manual operation not possible)., Rated operating current AC-3 380 V 400 V: Ie= 150 A, Rated operating current AC-1 conventional thermal current, 3-pole, 50 - 60 Hz open at 40 °C: Ith = Ie= 190 A, encapsulated: Ith= 144 A, Rated operating current AC-1 conventional thermal current 1-pole open: Ith= 400 A, encapsulated: Ith= 360 A, max. rated operating power three-phase motors 50 - 60 Hz AC-3 220 V 230 V: P= 48 kW, 380 V 400 V: P= 75 kW, 660 V 690 V: P= 96 kW, max. rated operating power three-phase motors 50 - 60 Hz AC-4 220 V 230 V: P= 20 kW, 380 V 400 V: P= 33 kW, 660 V 690 V: P= 48 kW, contact configuration S = normally open: 2 S, contact configuration Ö = normally closed: 2 Ö, notes: switching elements according to EN 50012., integrated protective circuit in the Control electronics., With mirror contact., Current type AC/DC: Alternating current operation
Property | Value |
Number of normally open contacts as main contacts: | 3 |
Number of auxiliary contacts as normally closed contacts: | 2 |
Number of auxiliary contacts as normally open contacts: | 2 |
Rated operating power at AC-3, 400 V: | 75 kW |
Rated operating power at AC-4, 400 V: | 33 kW |
Rated operating current Ie at AC-1, 400 V: | 190 A |
Rated operating current Ie at AC-3, 400 V: | 150 A |
Rated operating current Ie at AC-4, 400 V: | 65 A |
Type of voltage for actuation: | AC |
Rated control supply voltage Us at AC 50 Hz: | 110 V |
Rated control supply voltage Us at AC 60 Hz: | 120 V |
Type of connection main circuit: | Screw connection |
Suitable for series installation: | no |
Rated operating power NEMA: | 93 kW |