Load disconnector, Product range: Load disconnector, main switch, maintenance switch, Type code: DMM, STOP function: EMERGENCY STOP function, with red rotary handle and yellow locking ring, Note: in CI-K5 housing, Information on scope of delivery: Auxiliary switch contact can be retrofitted., 3-pole, Note: 1 padlock, 5 mm, Lockability: lockable in 0 position, Protection class: IP65, Design: surface mounting, Rated operating power AC-23A, 50 - 60 Hz 400 V: P = 80 kW, Rated continuous current: Iu = 160 A, Standards and regulations: IEC/EN 60947,0660, IEC/EN 60204, Load disconnector according to IEC/EN 60947-3
Property | Value |
Number of poles: | 3 |
Rated operational power at AC-23, 400 V: | 80 kW |
Rated continuous current Iu: | 160 A |
Max. Rated operating voltage Ue at AC: | 690 V |
Design as EMERGENCY STOP device: | yes |
Protection class (IP), front: | IP65 |
Connection type main circuit: | screw connection |
Device design: | Complete device in housing |
Design of the actuating element: | short rotary handle |
Suitable for floor mounting: | yes |
Conditional rated short-circuit current Iq: | 50 kA |
Motor drive integrated: | no |
Suitable for front mounting 4-hole: | no |
Version as maintenance/repair switch: | yes |
Voltage release optional: | no |
Suitable for front mounting central: | no |
Suitable for intermediate installation: | no |
Suitable for distribution board installation: | no |
Version as main switch: | yes |
Version as safety switch: | no |
Motor drive optional: | no |
Lockable: | yes |
Version as reversing switch: | no |
Rated short-time withstand current Icw: | 2.5 kA |
Color of the actuating element: | red |
Rated operating voltage: | 690 V |
Rated continuous current at AC-21, 400 V: | 160 A |
Number of switches: | 1 |
Rated continuous current at AC-23, 400 V: | 140 A |
Protection class (NEMA): | 12 |
Features
HAB
DMM-160/3/I5/PR
Manufacturer
HAN
172794
GTIN
4015081694594
Connection type main circuit
Screw connection
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
Yes
Designed as a safety switch
No
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Short twist grip
Conditional rated short-circuit current Iq
50kA
Rated operational power at AC-23, 400 V
80kW
Rated operating voltage
690V
Rated continuous current Iu
160A
Rated continuous current at AC-21, 400 V
160A
Rated continuous current at AC-23, 400 V
140A
Rated short-time withstand current Icw
2.5kA
Color of the actuator
Red
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
No
Suitable for intermediate construction
No
Device type
Complete device in housing
Max. rated operating voltage Ue at AC
690V
Motor drive integrated
No
Motor drive optional
No
Number of poles
3
Protection class (IP), front
IP65
Protection class (NEMA)
12
Voltage release optional
No
Lockable
Yes