Main switch, range: main switch, maintenance switch, repair switch, type code: P3, STOP function: HALT function, with black rotary handle and locking ring, 3-pole + N, lockability: lockable in 0 position, protection class: front IP65, design: intermediate installation, rated operating power AC-23A, 50 - 60 Hz 400 V: P = 55 kW, rated continuous current: Iu = 100 A, standards and regulations: IEC/EN 60947,0660, IEC/EN 60204, CSA, UL, load-break switch according to IEC/EN 60947-3, NEMA12
Property | Value |
Number of poles: | 4 |
Rated operating power at AC-23, 400 V: | 55 kW |
Number of auxiliary contacts as normally closed: | 1 |
Number of auxiliary contacts as normally open: | 1 |
Rated continuous current Iu: | 100 A |
Max. Rated operating voltage Ue at AC: | 690 V |
Version as EMERGENCY STOP device: | no |
Protection class (IP), front: | IP65 |
Connection type main circuit: | Screw connection |
Device design: | Built-in device, fixed installation technology |
Design of the actuating element: | Door coupling rotary drive |
Suitable for floor mounting: | no |
Conditional rated short-circuit current Iq: | 80 kA |
Motor drive integrated: | no |
Suitable for front mounting 4-hole: | no |
Version as maintenance/repair switch: | yes |
Voltage release optional: | no |
Suitable for front mounting central: | no |
Suitable for intermediate installation: | no |
Suitable for distribution board installation: | no |
Version as main switch: | yes |
Version as safety switch: | no |
Motor drive optional: | no |
Lockable: | yes |
Version as reversing switch: | no |
Rated short-time withstand current Icw: | 2 kA |
Color of the actuating element: | black |
Rated operating voltage: | 690 V |
Rated operating power at AC-3, 400 V: | 37 kW |
Switching capacity at 400 V: | 55 kW |
Rated continuous current at AC-21, 400 V: | 100 A |
Number of Switch: | 1 |
Rated continuous current at AC-23, 400 V: | 100 A |
Protection class (NEMA): | 1 |
Features
HAB
P3-100/V/SVB-SW/N/HI11
Manufacturer
HAN
083962
GTIN
4015080839620
Connection type main circuit
Screw connection
Number of auxiliary contacts as normally open
1
Number of auxiliary contacts as normally closed
1
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
No
Designed as a safety switch
No
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Door coupling rotary drive
Conditional rated short-circuit current Iq
80kA
Rated operational power at AC-23, 400 V
55kW
Rated operational power at AC-3, 400 V
37kW
Rated operating voltage
690V
Rated continuous current Iu
100A
Rated continuous current at AC-21, 400 V
100A
Rated continuous current at AC-23, 400 V
100A
Rated short-time withstand current Icw
2kA
Color of the actuator
Black
Suitable for floor mounting
No
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
No
Suitable for intermediate construction
No
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
690V
Motor drive integrated
No
Motor drive optional
No
Number of poles
4
Switching capacity at 400 V
55kW
Protection class (IP), front
IP65
Protection class (NEMA)
1
Voltage release optional
No
Lockable
Yes
No reviews yet — your comment may be first.