Motor protection switch complete device (basic device and electronic trip unit) according to IEC60947-4-1, electronic wide-range overload protection (4:1), phase failure and asymmetry protection, adjustable trip class, high short-circuit breaking capacity, isolator function, lockable in 0 position. Flexible adjustment of the current range through exchangeable electronic trip units. Can be expanded with auxiliary switch, voltage release, current limiter, door coupling handles. World market device, ATEX approval
Property | Value |
Number of poles: | 3 |
Rated operating voltage: | 690 V |
Rated continuous current Iu: | 12 A |
Overload release current setting: | 3 to 12 A |
Triggering technology: | electronic |
Phase failure sensitive: | yes |
Connection type main circuit: | screw connection |
Device design: | Built-in device, fixed installation technology |
Protection class (IP): | IP20 |
Width: | 45 mm |
Setting range of the instantaneous short-circuit release: | 186 A |
With integrated auxiliary switch: | no |
With integrated undervoltage release: | no |
Height: | 120 mm |
Depth: | 101 mm |
Design of the actuating element: | Rotary knob |
With thermal protection: | no |
Features
HAB
PKE12/AK/XTU-12 3-12A
Manufacturer
HAN
158243
GTIN
4015081548316
Connection type main circuit
Screw connection
Design of the actuating element
Rotary knob
Triggering technology
Electronic
Rated operating voltage
690V
Rated continuous current Iu
12A
Width
45 mm
Setting range of the instantaneous short-circuit release
186 A
Device type
Built-in device Fixed installation technology
Height
120 mm
With integrated auxiliary switch
No
With integrated undervoltage release
No
With thermal protection
No
Sensitive to phase failure
Yes
Number of poles
3
IP protection)
IP20
Depth
101 mm
Overload release current setting
3 to 12 A