Description
Features
Reviews
For the protection of consumer systems against transient overvoltages caused by direct and indirect lightning strikes, as well as switching operations, application according to IEC 60364-5-53 section 534, test classes I, II according to IEC 61643-1, SPD type T1, T2 according to EN 61643-11, lightning protection class III and IV according to IEC 62305, version without remote signaling
Property | Value |
Maximum continuous voltage AC: | 280 V |
Lightning impulse current (10/350 µs): | 12.5 kA |
Protection level: | 1.5 kV |
Test class: | Type 1 and 2 |
Number of poles: | 3 |
Nominal voltage AC: | 280 V |
Size: | 3 TE |
Remote signaling: | no |
Signaling on the device: | optical |
Network type TN-CS: | yes |
Network type DC: | no |
Network type TN: | yes |
Energetically coordinated protection effect for the end device: | no |
Mounting type: | DIN rail TH35 |
Network type TT: | no |
Specific energy (W/R): | 39.1 kJ/Ohm |
Integrated back-up fuse: | no |
Max. Conductor cross-section rigid (single/multi-wire): | 25 mm² |
Max. conductor cross-section flexible (fine-stranded): | 35 mm² |
Network type other: | yes |
Network type TN-C: | yes |
Network type IT: | no |
Network type TN-S: | yes |
Protection level L-PE: | 1.5 kV |
Protection class (IP): | IP20 |
Features
Max. conductor cross-section rigid (single/multi-wire)
25 mm²
Max. conductor cross-section flexible (fine-stranded)
35 mm²
Lightning surge current (10/350 µs)
12.5 kA
Protection level
1.5 kV
Network form TT
No
Network type TN-S
Yes
Network form TN
Yes
Network type TN-C
Yes
Network type TN-C-S
Yes
Network type DC
No
Integrated backup fuse
No
Network type IT
No
HAB
SPBT12-280/3 TN-C 3-pin
Manufacturer
HAN
158330
GTIN
4015081548880
Size
3 HP
Highest continuous voltage AC
280V
Mounting type
DIN rail TH35
Nominal voltage AC
280V
Number of poles
3
IP protection)
IP20
Signaling on the device
Optical
No reviews yet — your comment may be first.