Description
Features
Reviews
Control transformer, range: single-phase control transformers ST., basic function: single-phase control, isolating and safety transformers STI, STZ, nominal input voltage: 400 ± 5 % V, nominal output voltage: 230 V, nominal power: 3 kVA, short-time power: 11.5 kVA, protection class: IP00, standards and regulations built and tested according to: IEC/EN 61558-2-2/2-4/2-6,0570 Part 2-2,0570 Part 2-6 (safety transformers),0570 Part 2-4 (isolating transformers), can be used according to: IEC/EN 60204-1, ÖVE-EN 13,0113,0100 Part 410
| Property | Value |
| Rated apparent power: | 3000 VA |
| Height: | 255 mm |
| Width: | 230 mm |
| Depth: | 170 mm |
| Primary voltage 1: | 400 V |
| Secondary voltage 1: | 230 V |
| Protection class (IP): | IP00 |
| Suitable for series installation: | no |
| Short-circuit proof: | no |
| Designed as an isolating transformer: | yes |
| Relative short-circuit voltage uk: | 2.1 % |
| Toroidal core: | no |
| Insulating material class according to IEC 85: | B |
| Suitable for circuit board mounting: | no |
| Designed as a safety transformer: | yes |
| Designed as an economy transformer: | no |
| Conductor material: | copper |
Features
Short circuit proof
No
Conductor material
Copper
Secondary voltage 1
230 V
HAB
STI3.0 (400/230) 3.0kVA
Manufacturer
HAN
035260
GTIN
4015080352600
Width
230 mm
Suitable for series installation
No
Height
255 mm
IP protection)
IP00
Depth
170 mm