Main switch, product range: main switch, maintenance switch, repair switch, type code: T3, STOP function: EMERGENCY STOP function, with red rotary handle and yellow locking ring, 3-pole, protection class: front IP65, design: intermediate installation, switching angle: 90 °, rated operating power AC-23A, 50 - 60 Hz 400 V: P = 15 kW, rated continuous current: Iu = 32 A, 2 unit(s), standards and regulations: IEC/EN 60947,0660, IEC/EN 60204, CSA, UL, load-break switch according to IEC/EN 60947-3
Property | Value |
Number of poles: | 3 |
Rated operating power at AC-23, 400 V: | 15 kW |
Number of auxiliary contacts as normally open: | 1 |
Rated continuous current Iu: | 32 A |
Max. Rated operating voltage Ue at AC: | 690 V |
Version as EMERGENCY STOP device: | yes |
Protection class (IP), front: | IP65 |
Connection type main circuit: | Screw connection |
Device design: | Built-in device, fixed installation technology |
Design of the actuating element: | Door coupling rotary drive |
Suitable for floor mounting: | yes |
Conditional rated short-circuit current Iq: | 1 kA |
Motor drive integrated: | no |
Suitable for front mounting 4-hole: | no |
Version as maintenance/repair switch: | yes |
Voltage release optional: | no |
Suitable for front mounting central: | no |
Suitable for intermediate installation: | yes |
Suitable for distribution board installation: | no |
Version as main switch: | yes |
Version as safety switch: | no |
Motor drive optional: | no |
Lockable: | yes |
Version as reversing switch: | no |
Rated short-time withstand current Icw: | 0.65 kA |
Color of the actuating element: | red |
Rated operating voltage: | 690 V |
Rated operating power at AC-3, 400 V: | 11 kW |
Switching capacity at 400 V: | 15 kW |
Rated continuous current at AC-21, 400 V: | 32 A |
Number of Switch: | 1 |
Protection class (NEMA): | 12 |
Features
HAB
T3-2-15169/V/SVB
Manufacturer
HAN
008653
GTIN
4015080086536
Connection type main circuit
Screw connection
Number of auxiliary contacts as normally open
1
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
Yes
Designed as a safety switch
No
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Door coupling rotary drive
Conditional rated short-circuit current Iq
1kA
Rated operational power at AC-23, 400 V
15kW
Rated operational power at AC-3, 400 V
11kW
Rated operating voltage
690V
Rated continuous current Iu
32 A
Rated continuous current at AC-21, 400 V
32 A
Rated short-time withstand current Icw
0.65kA
Color of the actuator
Red
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
No
Suitable for intermediate construction
Yes
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
690V
Motor drive integrated
No
Motor drive optional
No
Number of poles
3
Switching capacity at 400 V
15kW
Protection class (IP), front
IP65
Protection class (NEMA)
12
Voltage release optional
No
Lockable
Yes