Main switch, product range: main switch, maintenance switch, repair switch, type code: T3, STOP function: HALT function, with black rotary handle and locking ring, 3-pole + N, lockability: lockable in 0 position, protection class: IP65, design: surface mounting, switching angle: 90 °, rated operating power AC-23A, 50 - 60 Hz 400 V: P = 15 kW, rated continuous current: Iu = 32 A, 3 unit(s), standards and regulations: IEC/EN 60947,0660, IEC/EN 60204, load-break switch according to IEC/EN 60947-3
Property | Value |
Number of poles: | 4 |
Rated operating power at AC-23, 400 V: | 15 kW |
Number of auxiliary contacts as normally closed: | 1 |
Number of auxiliary contacts as normally open: | 1 |
Rated continuous current Iu: | 32 A |
Max. Rated operating voltage Ue at AC: | 690 V |
Version as EMERGENCY STOP device: | no |
Protection class (IP), front: | IP65 |
Connection type main circuit: | screw connection |
Device design: | Complete device in housing |
Design of the actuating element: | Door coupling rotary drive |
Suitable for floor mounting: | yes |
Conditional rated short-circuit current Iq: | 1 kA |
Motor drive integrated: | no |
Suitable for front mounting 4-hole: | no |
Version as maintenance/repair switch: | yes |
Voltage release optional: | no |
Suitable for front mounting central: | no |
Suitable for intermediate installation: | no |
Suitable for distribution board installation: | no |
Version as main switch: | yes |
Version as safety switch: | no |
Motor drive optional: | no |
Lockable: | yes |
Version as reversing switch: | no |
Rated short-time withstand current Icw: | 0.65 kA |
Color of the actuating element: | black |
Rated operating voltage: | 690 V |
Rated operating power at AC-3, 400 V: | 11 kW |
Switching capacity at 400 V: | 15 kW |
Rated continuous current at AC-21, 400 V: | 32 A |
Number of Switch: | 1 |
Rated continuous current at AC-23, 400 V: | 32 A |
Protection class (NEMA): | 12 |
Features
HAB
T3-3-15680/I2/SVB-SW
Manufacturer
HAN
207203
GTIN
4015082072032
Connection type main circuit
Screw connection
Number of auxiliary contacts as normally open
1
Number of auxiliary contacts as normally closed
1
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
No
Designed as a safety switch
No
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Door coupling rotary drive
Conditional rated short-circuit current Iq
1kA
Rated operational power at AC-23, 400 V
15kW
Rated operational power at AC-3, 400 V
11kW
Rated operating voltage
690V
Rated continuous current Iu
32 A
Rated continuous current at AC-21, 400 V
32 A
Rated continuous current at AC-23, 400 V
32 A
Rated short-time withstand current Icw
0.65kA
Color of the actuator
Black
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
No
Suitable for intermediate construction
No
Device type
Complete device in housing
Max. rated operating voltage Ue at AC
690V
Motor drive integrated
No
Motor drive optional
No
Number of poles
4
Switching capacity at 400 V
15kW
Protection class (IP), front
IP65
Protection class (NEMA)
12
Voltage release optional
No
Lockable
Yes