Optional accessories for the NZM circuit breaker series offer an extensive portfolio of application options for worldwide use. Installation is flexible and simple thanks to modular function groups. Notes: Combination of separate delay unit and special release. Can be used for EMERGENCY STOP devices in conjunction with EMERGENCY STOP buttons. Not UL/CSA approved. Voltage drops of less than 0.06-16 s do not switch off the NZM circuit breaker or N switch disconnector. Delay time adjustable: 70ms- 4 s. With additional external capacitor: 30,000 F 35 V up to 8 s, 90,000 F 35 V up to 16 s. A special release is required. Cannot be installed at the same time as a separate leading auxiliary switch NZM..-XHIV or shunt release NZM..-XA.. Delay device for separate installation. Fastening: top hat rail or screws. Use a control transformer for other operating voltages. Can be used for: NZM1 (-4), 2 (-4), 3 (-4), 4 (-4), N (S) 1 (-4), 2 (-4), 3 (-4), 4 (-4), 50/60 Hz 220V-240V, 380V-440V, 480V-550V, DC/AC 24 V
Property | Value |
Design of the electrical connection: | Screw connection |
Suitable for circuit breakers: | no |
Suitable for motor protection switches: | no |
Suitable for load switches: | yes |
Suitable for overload relays: | no |
Type of voltage for actuation: | AC/DC |
Delayed: | yes |
Rated control supply voltage Us at AC 50 Hz: | 24 to 550 V |
Rated control supply voltage Us at AC 60 Hz: | 24 to 550 V |
Rated control supply voltage Us at DC: | 24 V |