Complete meter cabinet according to AR-N 4101:2015-09, pre-wired and equipped with switching devices. Meter field equipped with BKE-A meter plate, 10mm² Lower connection compartment with 5-pin. Busbar system 12x5mm, incl. 16mm² connection terminals for accommodating selective main circuit breakers up to 63 A Functional space for additional utility company applications covered with lockable blind strip RJ45 connection socket insulated, packed loose Upper connection space with main line terminal 5x25mm², finger-safe Distribution panel with 5 x 12 TE with 2x PEN rail in plug-in technology Distribution panel equipped with: 2 pieces PXF-40/4/003-A 12 pieces PXL-B16/1, 2x6 circuit breakers connected to residual current device via phase rail EVG-3PHAS/N/8MODUL/LS 1 piece, Schuko sockets 230V Installation Circuit breaker rows covered with blind strip Wiring: 10mm² between main line terminal and FI/PEN rail Connection between residual current device and circuit breaker row APZ: Yes, installed in the distribution panel below, including protective hose for data cable Protection class: IP31 Dimensions mm: Height 1100, width 550, depth 225
Property | Value |
Number of meter spaces: | 1 |
Number of distribution rows: | 7 |
Number of fields: | 2 |
Height: | 1101 mm |
Width: | 551 mm |
Depth: | 225 mm |
Protection class (IP): | IP31 |
Version: | eHZ |
Lower connection compartment: | with 5-pole busbar |
Material: | Sheet steel |
With mounting plate: | no |
Mounting type: | Surface-mounted |
Installation width: | 550 mm |
Installation height: | 1100 mm |
Installation depth: | 225 mm |