1 normally open contact not potential-free 16A/250V AC, 230V LED lamps up to 600W, ESL up to 200W, incandescent lamps up to 2300W. Control voltage 230V and/or 8..230V UC. Switch-off warning and button permanent light can be switched on. Standby loss only 0.7 watts. With ESL optimization and multifunction. Modular device for mounting on DIN-EN 60715 TH35 mounting rail. 1 division unit = 18mm wide, 58mm deep. Contact switching at zero crossing to protect the contacts and lamps. The noiseless electronics do not bother the most sensitive ear - in contrast to many synchronous motors with mechanical gears. By using a bistable relay, there is no coil power loss and no heating as a result, even when switched on. After installation, wait for the automatic short synchronization before connecting the switched consumer to the mains. Control, supply and switching voltage 230V. Also with galvanically isolated universal control voltage 8..230V UC. For 3- and 4-wire circuits, can be switched on later, with attic lighting for 4-wire circuits. Automatic detection of the circuit type. Glow lamp current up to 50mA, depending on the ignition voltage of the glow lamps. Exact time setting 1 to 30 minutes with minute scale. Permanent light switch with the large rotary switch. After a power failure in the TLZ function setting, the lighting is switched on again if the time has not yet expired. With double connections for button and lamp, so that connections can be made either at the top and bottom or just at the bottom. When the switch-off warning is switched on, the lighting flickers approx. 30 seconds before the time expires and a total of 3 times at increasingly shorter intervals. If the permanent light button is switched on, you can press the button for longer than 1 second to set the light to permanent, which switches off automatically after 60 minutes, or you can press the button for longer than 2 seconds to switch it off. If the permanent light button and switch-off warning button are switched on, the switch-off warning is only given after the permanent light is switched off. If all or part of the ESL energy-saving lamps are switched on, then set the switch-off warning and the permanent light button on the right-hand ESL side of the rotary switch. Within the first second after switching on or switching on again, the time for the TLZ functions can be extended by briefly pressing the button up to 3 times (pumping). Each press adds the set time once. With multifunction: Can be switched to the functions ES (impulse switch), ER (relay) and ESV (impulse switch with release delay). In the ESV function, the times (t) that can be set using the middle rotary switch correspond to the following values: 1 = 2 min, 2 = 5 min, 3 = 10 min, 4 = 15 min, 6 = 25 min, 8 = 35 min, 10 = 45 min, 12 = 60 min, 20 = 90 min, 30 = 120 min. After the set delay time has elapsed, the device switches off automatically if the manual off command has not been given. Switch-off advance warning and button permanent light can also be switched on with ESV. If the permanent light is forgotten, it switches off after 2 hours. , Modular device for mounting on DIN-EN 60715 TH35 rail., 1 pitch unit = 18 mm wide, 58 mm deep., Contact switching at zero crossing to protect the contacts and lamps. , The noiseless electronics do not bother even the most sensitive ear - in contrast to many synchronous motors with mechanical gears., By using a bistable relay, there is no coil power loss and no heating as a result, even when switched on. , After installation, wait for the automatic short synchronization before connecting the switched consumer to the mains., Control, supply and switching voltage 230 V. Additionally with g
Property | Value |
Width in modular divisions: | 1 |
Off delay: | 1 to 12 min |
Function: | electronic with switch-off warning |
Mounting type: | DIN rail |
Control voltage 1: | 230 V |
Rated switching current: | 1.6 A |
Control voltage type 1: | AC |
Current surge function selectable: | yes |
Control voltage 2: | 8 to 230 V |
Control voltage type 2: | AC/DC |
Frequency of control voltage 1: | 50 Hz |
Circuit type: | 3- and 4-wire circuit |
Switch-off warning: | flickering |
Follow-up switching: | can be switched on again + continuous light + time extension |
Type of supply voltage: | AC |
Installation depth: | 58 mm |
Button glow lamp current: | 50 mA |
Supply voltage: | 230 V |
Max. incandescent lamp load: | 400 W |
Max. Fluorescent lamp load (parallel compensated): | 400 VA |
Number of contacts as normally open: | 1 |