Description
Features
Reviews
Surge arrester type 3, for 1-phase TNS and TT networks (polarity neutral). Varistor between L and N and a spark gap between N and PE, for installation in a flush-mounted box. Acoustic signal in the event of varistor failure. Cable length L, N and PE 150 mm, dimensions: L=48.5 mm, W=29 mm, H=10.5 mm. Design: with acoustic test plug to check the buzzer.
| Property | Value |
| Nominal voltage AC: | 230 V |
| Maximum continuous voltage AC: | 275 V |
| Mounting type: | Wall socket |
| With remote signaling contact: | no |
| Nominal discharge current (8/20) (LN): | 3 kA |
| Total discharge current (8/20) (L+N-PE): | 6 kA |
| Protection level LN: | 1.65 kV |
| Protection level L-PE/N-PE: | 1.5 kV |
| Number of poles: | 1 |
| Signaling on the device: | acoustic |
| Test class type 3: | yes |
| With interference filter: | no |
| Protection class (IP): | IP20 |
Features
With remote signaling contact
No
Protection level L-N
1.65 kV
HAB
7P.36.8.275.2003
Manufacturer
HAN
7P.36.8.275.2003
GTIN
8012823407890
Highest continuous voltage AC
275V
Mounting type
Wall socket
Nominal voltage AC
230V
Number of poles
1
IP protection)
IP20
Signaling on the device
Acoustically
No reviews yet — your comment may be first.
All reviews 0