Reviews
Surge arrester type 3, for 1-phase TNS and TT networks. Varistor between L and N and a spark gap between N and PE, for DIN rail mounting. LED signal on the front and status feedback via output contact in the event of varistor failure. Contact type 1 changeover contact, rated current 0.5 A, contact material AgNi hard gold-plated.
Property | Value |
Nominal voltage AC: | 230 V |
Maximum continuous voltage AC: | 275 V |
Mounting type: | DIN rail TH35 |
With remote signaling contact: | no |
Nominal discharge current (8/20) (LN): | 3 kA |
Total discharge current (8/20) (L+N-PE): | 3 kA |
Nominal load current: | 16 A |
Protection level LN: | 1 kV |
Protection level L-PE/N-PE: | 1.5 kV |
Number of poles: | 1 |
Signaling on the device: | optical |
Test class type 3: | yes |
With interference filter: | no |
Max. conductor cross-section rigid (single/multi-wire): | 6 mm² |
Max. conductor cross-section flexible (fine-stranded): | 4 mm² |
Protection class (IP): | IP20 |
Total discharge current (8/20) (L1+L2+L3+N-PE): | 6 kA |
Features
Max. conductor cross-section rigid (single/multi-wire)
6 mm²
Max. conductor cross-section flexible (fine-stranded)
4 mm²
With remote signaling contact
No
Nominal load current
16 A
Protection level L-N
1 kV
Manufacturer
HAN
7P.37.8.275.1003
GTIN
8012823388427
Highest continuous voltage AC
275V
Mounting type
DIN rail TH35
Nominal voltage AC
230V
Number of poles
1
IP protection)
IP20
Signaling on the device
Optical