Description
Features
Reviews
Type 2, network configuration: TNS 4+0 circuit, Imax / pole = 40 kA, 4 modules, with remote signaling contact, modular design, mounting on 35 mm DIN rail
Nominal voltage | UN | 230 V AC / 400 V AC |
Maximum continuous voltage | UC | 275 V AC |
Nominal discharge current (8/20 µs) | In | 20 kA |
Maximum discharge current (8/20 µs) | Imax | 40 kA |
Protection level | Up | <, 1.3 kV |
Short-circuit strength | ISCCR | 25 kA |
Maximum back-up fuse | 125 A gL/gG | |
TOV behavior | UT | 335 V (5 s / strength) |
TOV behavior | UT | 440 V (120 min / safe failure) |
Response time | tA | 25 ns |
Connection cross-section rigid | 4 mm2 … 35 mm2 | |
Connection cross-section flexible | 4 mm2 … 25 mm2 | |
Fault indicator | with | |
remote signaling indicator | potential-free changeover contact | |
Operating voltage/operating current AC/DC (FM) | 250 V/0.5 A AC, 250 V/0.1 A DC | |
Connection cross-section remote signaling | 1.3 mm2 | |
Protection class | IP 20 | |
Operating temperature | -40 °C … + 85 °C | |
Permissible humidity | RH | 5% ... 95% |
Mounting on | 35 mm DIN rail |