Restart RD PRO switch-on module for mounting on Gewiss residual current circuit breakers (RCCB) of the IDP series 2- and 4-pole up to a rated current of 100A. With the RESTART PRO module, the residual current circuit breakers are automatically switched back on after being triggered. The system is switched back on after an automatic insulation test by the RESTART module. If there is a constant system error, no switch-on attempt is made. The system is checked every 2 minutes by RESTART PRO. If the system assumes a safe value, RESTART PRO switches the residual current circuit breaker back on. It is not switched on in the event of an existing error. The power supply is integrated in the RESTART module and is provided by the cables either at the bottom or top of the residual current circuit breaker without any additional parts. LEDs and an auxiliary contact signal the operating states of the RESTART module. The RESTART module can be switched on or off using a simple slide switch. Rated residual current: 0.1-0.3-0.5A, type: A. Compatible with the BUS module.
| Property | Value |
| Rated residual current: | 0.30 A |
| Width in modular spacing: | 2 |
| Protection class (IP): | IP20 |
| Additional devices integrated: | Self-test, automatic restart and auxiliary switch |
| Mounting type: | DIN rail |
| Installation depth: | 72 mm |
| Rated voltage of additional device: | 230 V |
| Frequency: | 50 Hz |
| Control voltage type of additional device: | AC |
| Additional devices fitted at the factory: | Monitoring unit with automatic restart |