FI/LS switch, mains voltage-independent residual current circuit breaker with built-in overcurrent protection (RCBO) in accordance with EN61009-1. Suitable for the subsequent installation of 2 additional devices and/or combinations with modules for automatic restart. The switch lever can be sealed in the switched-on and off state or can be locked with a lever lock (order accessories separately) for a padlock. With integrated residual current display and fold-down label plate. Connection (max): 35 mm² with insulated plug-in protection. The connection screws can be provided with a sealable cover (order accessories separately).
Property | Value |
Tripping characteristic: | B |
Rated current: | 25 A |
Rated residual current: | 0.3 A |
Rated voltage: | 230 V |
Frequency: | 50 Hz |
Number of poles (total): | 2 |
Width in modular spacing: | 2 |
Fault current type: | A |
Installation depth: | 72 mm |
Rated breaking capacity according to IEC 60947-2: | 15 kA |
Surge current strength: | 0.25 kA |
Degree of protection (IP): | IP20 |
Energy limitation class: | 3 |
Overvoltage category: | 3 |
Degree of pollution: | 2 |
Switching neutral conductor: | no |
Number of protected poles: | 2 |
Type of voltage: | AC |
False tripping protection: | no |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Rated breaking capacity according to EN 61009: | 10 kA |
Rated short-circuit breaking capacity Icn according to EN 61009-1: | 10 kA |
Shut-down characteristic: | undelayed |
With locking device: | no |
Ambient temperature during operation: | -25 to 40 °C |
Connectable conductor cross-section, single-wire: | 35 mm² |
Connectable conductor cross-section, stranded: | 35 mm² |
Features
Shutdown characteristics
Without delay
Rated short-circuit breaking capacity Icn according to EN 61009-1
10 kA
HAB
MDC100 FI/LS B25/0.3A 2P A 10KA 2TE
Manufacturer
HAN
GW95339
GTIN
8011564299320
Connectable conductor cross-section solid
35 mm²
Connectable conductor cross-section stranded
35 mm²
Number of protected poles
2
Trigger characteristics
B
Rated breaking capacity according to EN 61009
10kA
Rated breaking capacity according to IEC 60947-2
15kA
Rated residual current
0.3A
Rated insulation voltage Ui
500V
Rated voltage
230V
Rated impulse withstand voltage Uimp
4kV
Rated current
25A
Width in pitch units
2
Installation depth
72 mm
Energy limitation class
3
False trigger protection
No
Residual current type
A
Frequency
50Hz
With locking device
No
Switching neutral conductor
No
Number of poles (total)
2
IP protection)
IP20
Voltage type
AC
Surge current strength
0.25kA
Ambient temperature during operation
-25 to 40 °C
Degree of contamination
2
Overvoltage category
3