Measuring and testing device for testing the effectiveness of protective measures on stationary electrical installations after commissioning, repair, expansion and during a repeat test (DGUV Regulation 3). The PROFITEST MF TECH offers all measuring and testing functions for testing the effectiveness of protective measures on stationary electrical installations - both with predefined and optionally with programmable test sequences that are required in accordance with the test standards according to IEC 60364-6 (DIN0100-600) and EN 50110-1 (DIN0105-100). Measurement category 300 V CAT IV / 600 V CAT III. The PROFITEST MF TECH makes your investment decision easy. With the test scope perfectly tailored to your requirements for the electrical professional, it is the ideal testing device for your everyday life - day after day. With its optimal operation and the storage concept, creating a test report is quick and easy. This saves you time with every test and allows you to carry out more tests every day. Once you have created system structures, you can use them across all PROFITEST devices. This means that every employee always carries out exactly the same tests. And with the PROFITEST service guarantee, you can be sure that your test device will still be up to date in 10 years. Context-sensitive color graphic display Measurement and test sequence - easy creation of the system structure / measure & save / generate protocol Pre-configured and self-programmable test sequences for quickly testing electrical systems Storage concept for up to 50,000 data records Testing of all current universal current-sensitive RCDs, RDC-DD, RCMB Operator protection through PE detection when used with finger contact Future-oriented connectivity. Intuitive operation thanks to innovative user guidance Efficient working thanks to test sequences Standard-compliant testing in accordance with ZVEH Legally compliant logging thanks to interfaces Wide range of applications thanks to a wide range of measurement options Comfortable working without the hassle of replugging the measuring cables Can be used internationally thanks to language selection Future-proof thanks to firmware updates on site Cascadable, future-proof software concept On-site assistance thanks to help function with connection diagrams. Tests of the effectiveness of protective measures on fixed electrical installations in accordance with IEC 60364-6 (DIN0100-600), EN 50110-1 (DIN0105-100) and other country-specific standards. Testing of e-charging points according to EN 61851-1 (DIN0122-1).. Wide-range measuring device for all alternating current and three-phase networks with voltages from 65 to 500 V and frequencies from 15.4 to 420 Hz Loop and network impedance measurement with DC pre-magnetization Measurement of insulation resistance with nominal voltage, with variable or increasing test voltage Low-resistance measurement with automatic polarity reversal Testing of residual current devices and special RCD circuit breakers (selective S, SRCDs, PRCDs, Schukomat, Sidos, type G/R, AC, A, A-EV,F, F-EV, B, B+, B-MI) Testing of residual current (RCD) protective circuits in IT networks Testing of RDC-DD according to IEC 62955 and RCMB according to DIN EN 62752 Measuring the earthing resistance (network operation) Standard testing of e-charging stations according to IEC 61851-1 in conjunction with the test adapter Metraline PRO-TYP EM Auto function test sequences USB interface Push-print function – sending the measured value after the measurement has been completed. 1x PROFITEST MF TECH 1x safety plug insert (country-specific) 1x 2-pin measuring adapter and 1x cable for extension to 3-pin adapter (PRO-A3-II) 2x crocodile clips 1x shoulder strap 1x set of batteries (Z502H) 1x charger (Z502R) 1x short operating instructions 1x safety information sheet 1x DAkkS calibration certificate 1x
Property | Value |
Display: | digital |
Insulation resistance measurement: | yes |
Surge arrester test: | yes |
Loop resistance/impedance measurement: | yes |
Internal network resistance measurement: | yes |
RCD/FI test: | yes |
RCD/FI test with increasing fault current: | yes |
RCD/FI analysis function: | yes |
Rotation field test: | yes |
Low resistance measurement: | yes |
Earthing measurement: | yes |
Selective earthing measurement: | no |
Earth loop measurement: | no |
Specific earthing measurement: | no |
Measured value memory: | yes |
Interface: | yes |
Printer connection: | no |
Limit value display: | yes |
Resistances of insulating floors and walls: | yes |
Loop measurement without RCD/FI triggering: | yes |
Determination of short-circuit current/overcurrent protection devices: | yes |
Integrated printer: | no |
Remote control of the test device: | yes |
Insulation resistance measurement with ramp function: | yes |
Curve shape for RCD/FI testing: | for residual current circuit breakers type A, F and type B, B+ |
Measurement of leakage currents with Adapter: | no |
Low-resistance measurement with ramp function: | yes |
PRCD test type S, type K: | yes |
Testing of e-charging stations, simulation of vehicle status: | yes |
Testing of IMDs and RCMs: | no |
Structured measured value memory: | yes |