Description
Features
Reviews
Residual current circuit breaker 1P+N 127V 6kA B-16A 30mA Type A QuickConnect. Residual current circuit breaker in accordance with DIN EN 61009-1 (VDE 0664-20) with QuickConnect terminal, on the outgoing circuit up to 20 A and on the incoming circuit up to 63 A, blue test button and residual current display. Easy individual removal from the phase busbar system. Suitable for the subsequent installation of additional equipment. Labeling option directly on the device.
Property | Value |
Triggering characteristic: | B |
Rated current: | 16 A |
Rated residual current: | 0.03 A |
Rated voltage: | 127 V |
Frequency: | 50 Hz |
Number of poles (total): | 2 |
Width in pitch units: | 2 |
Fault current type: | A |
Installation depth: | 68 mm |
Rated breaking capacity according to IEC 60947-2: | 6 kA |
Surge current strength: | 0.25 kA |
Degree of protection (IP): | IP20 |
Energy limitation class: | 3 |
Overvoltage category: | 3 |
Pollution degree: | 2 |
Switching neutral conductor: | yes |
Number of protected poles: | 1 |
Type of voltage: | AC |
False tripping protection: | no |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Rated short-circuit breaking capacity Icn according to EN 61009-1: | 6 kA |
Shutdown characteristics: | undelayed |
With locking device: | yes |
Ambient temperature during operation: | -25 to 40 °C |
Features
Shutdown characteristics
Without delay
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Manufacturer
HAN
ADS917D
GTIN
3250611011958
Number of protected poles
1
Trigger characteristics
B
Rated breaking capacity according to IEC 60947-2
6kA
Rated residual current
0.03A
Rated insulation voltage Ui
500V
Rated voltage
127V
Rated impulse withstand voltage Uimp
4kV
Rated current
16A
Width in pitch units
2
Installation depth
68 mm
Energy limitation class
3
False trigger protection
No
Residual current type
A
Frequency
50Hz
With locking device
Yes
Switching neutral conductor
Yes
Number of poles (total)
2
IP protection)
IP20
Voltage type
AC
Surge current strength
0.25kA
Ambient temperature during operation
-25 to 40 °C
Degree of contamination
2
Overvoltage category
3
No reviews yet — your comment may be first.
All reviews 0