Transformer and measuring cabinet, Univ.N, incl. base, 2050x800x400mm, Region South
Technical features:
Mounting typeSingle and series installation
Connection typewith 5-pole busbar
Number of meter spaces &le, 63 A0
Meter holder3-point system
Number of 3-point holders for SG/TRE0
Version of meter exchange plateSize 3
Ambient temperature0&hellip,20 °C
Height of installed product2050 mm
Width of installed product800 mm
Depth of installed product350 mm
IK coding of mechanical shock resistance09
RAL colorRAL 7035 - light gray
Surfacepowder-coated
Number of doors1
Door closing type3-point with swivel lever
Opening angle0 / 120 °
Busbar height30 mm
Busbar thickness10 mm
Busbar spacing185 mm
Busbar surfaceCopper untreated
Nominal voltage230/400 V
Network typeTN-S
Nominal current480 A
Total power loss under rated current73 W
Protection classProtection class II
Degree of protectionIP55
Insulation voltage600 V
Surge voltage strength6 kV
Surge current strength32 kA
Rated short-term current strength Icw22 kA
Property | Value |
Number of distribution rows: | 12 |
Number of fields: | 2 |
Height: | 2050 mm |
Width: | 800 mm |
Depth: | 350 mm |
Protection class (IP): | IP55 |
Lower connection compartment: | with 5-pole busbar |
Material: | Sheet steel |
With mounting plate: | no |
Mounting type: | Surface-mounted |
Installation width: | 800 mm |
Installation height: | 2050 mm |
Installation depth: | 350 mm |