Description
Features
Reviews
Load-disconnector with disconnection indicator 4P 1600A. Load-disconnector according to DIN EN 60947-3 for ON/OFF switching in systems. Built in a modular design for snapping onto a DIN-C top-hat rail or for mounting on a mounting plate.
| Property | Value |
| Number of poles: | 4 |
| Rated operating power at AC-23, 400 V: | 562 kW |
| Rated continuous current Iu: | 1600 A |
| Max. Rated operating voltage Ue at AC: | 415 V |
| Design as EMERGENCY STOP device: | no |
| Protection class (IP), front: | IP00 |
| Connection type main circuit: | Cable clamp |
| Device design: | Built-in device, fixed installation technology |
| Design of the actuating element: | long rotary handle |
| Suitable for floor mounting: | yes |
| Conditional Rated short-circuit current Iq: | 50 kA |
| Integrated motor drive: | no |
| Suitable for 4-hole front mounting: | no |
| Version as maintenance/repair switch: | yes |
| Voltage release optional: | no |
| Suitable for central front mounting: | no |
| Suitable for intermediate installation: | no |
| Suitable for Distribution board installation: | yes |
| Version as main switch: | yes |
| Version as safety switch: | yes |
| Motor drive optional: | no |
| Lockable: | yes |
| Version as reversing switch: | no |
| Rated short-time withstand current Icw: | 50 kA |
| Color of the actuating element: | black |
| Rated operating voltage: | 380 to 415 V |
| Switching capacity at 400 V: | 1053 kW |
| Rated continuous current at AC-21, 400 V: | 1600 A |
| Number of switches: | 1 |
| Rated continuous current at AC-23, 400 V: | 1000 A |
| Protection class (NEMA): | other |
Features
HAB
HA464 with disconnection indicator 4P 1600A
Manufacturer
HAN
HA464
GTIN
3250613119720
Connection type main circuit
Cable clamp
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
No
Designed as a safety switch
Yes
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Long rotary handle
Conditional rated short-circuit current Iq
50kA
Rated operational power at AC-23, 400 V
562kW
Rated operating voltage
380 to 415 V
Rated continuous current Iu
1600A
Rated continuous current at AC-21, 400 V
1600A
Rated continuous current at AC-23, 400 V
1000A
Rated short-time withstand current Icw
50kA
Color of the actuator
Black
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
Yes
Suitable for intermediate construction
No
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
415V
Motor drive integrated
No
Motor drive optional
No
Number of poles
4
Switching capacity at 400 V
1053kW
Protection class (IP), front
IP00
Protection class (NEMA)
Other
Voltage release optional
No
Lockable
Yes
No reviews yet — your comment may be first.