Load-break switch size x250 3-pole 250A. Load-break switch in accordance with DIN EN 60947-3 size x250, with magnetic (adjustable) release for switching electrical systems and networks. Mounted on mounting plate. The three different operating states can be identified by the position of the knob (ON = top, OFF = bottom, triggered = middle position). The switches have a mechanical test button. The function of the circuit breakers can be expanded using various accessories. Including phase barriers.
| Property | Value |
| Number of poles: | 3 |
| Rated operating power at AC-23, 400 V: | 112 kW |
| Rated continuous current Iu: | 250 A |
| Max. Rated operating voltage Ue at AC: | 415 V |
| Design as EMERGENCY STOP device: | yes |
| Protection class (IP), front: | IP40 |
| Connection type main circuit: | Cable clamp |
| Device design: | Built-in device, fixed installation technology |
| Design of the actuating element: | Toggle |
| Suitable for floor mounting: | yes |
| Integrated motor drive: | no |
| Suitable for front mounting 4-hole: | no |
| Version as maintenance/repair switch: | yes |
| Voltage release optional: | yes |
| Suitable for front mounting central: | no |
| Suitable for intermediate installation: | no |
| Suitable for distribution board installation: | yes |
| Version as main switch: | yes |
| Design as safety switch: | yes |
| Motor drive optional: | yes |
| Lockable: | yes |
| Design as reversing switch: | no |
| Rated short-time withstand current Icw: | 3 kA |
| Color of the actuating element: | black |
| Rated operating voltage: | 220 to 415 V |
| Switching capacity at 400 V: | 164 kW |
| Rated continuous current at AC-21, 400 V: | 250 A |
| Number of switches: | 1 |
| Protection class (NEMA): | other |
Features
Manufacturer
HAN
HCB250H
GTIN
3250613136796
Connection type main circuit
Cable clamp
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
Yes
Designed as a safety switch
Yes
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Gag
Rated operational power at AC-23, 400 V
112kW
Rated operating voltage
220 to 415 V
Rated continuous current Iu
250A
Rated continuous current at AC-21, 400 V
250A
Rated short-time withstand current Icw
3kA
Color of the actuator
Black
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
Yes
Suitable for intermediate construction
No
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
415V
Motor drive integrated
No
Motor drive optional
Yes
Number of poles
3
Switching capacity at 400 V
164kW
Protection class (IP), front
IP40
Protection class (NEMA)
Other
Voltage release optional
Yes
Lockable
Yes