Load break switch h3+ P630 4-pole 630A FTC. The load break switch in accordance with DIN EN 60947-3 separates the incoming and outgoing sides in electrical systems. The two different operating states can be identified by the position of the toggle (ON = top, OFF = bottom). A device for locking the switching state in the ON or OFF position is integrated and can be used with a standard padlock without additional accessories. A hinged cover with a captive quick-release screw enables access to the installation space for optional auxiliary contacts and other releases. Integrated accessories can be seen and identified via a viewing window without opening the hinged cover.
| Property | Value |
| Number of poles: | 4 |
| Rated operational power at AC-23, 400 V: | 508 kW |
| Rated continuous current Iu: | 630 A |
| Max. Rated operating voltage Ue at AC: | 690 V |
| Version as EMERGENCY STOP device: | yes |
| Protection class (IP), front: | IP40 |
| Connection type main circuit: | Cable clamp |
| Device design: | Built-in device, fixed installation technology |
| Design of the actuating element: | Toggle |
| Suitable for floor mounting: | yes |
| Integrated motor drive: | no |
| Suitable for front mounting 4-hole: | no |
| Version as Maintenance/repair switch: | yes |
| Voltage release optional: | yes |
| Suitable for front mounting central: | no |
| Suitable for intermediate installation: | no |
| Suitable for distribution board installation: | yes |
| Version as main switch: | yes |
| Version as safety switch: | no |
| Motor drive optional: | yes |
| Lockable: | yes |
| Version as reversing switch: | no |
| Rated short-time withstand current Icw: | 7.6 kA |
| Color of the actuating element: | gray |
| Rated operating voltage: | 220 to 690 V |
| Rated continuous current at AC-21, 400 V: | 630 A |
| Number of switches: | 1 |
| Rated continuous current at AC-23, 400 V: | 500 A |
| Protection class (NEMA): | other |
Features
HAB
HCW631AR h3+ P630 4 pole 630A
Manufacturer
HAN
HCW631AR
GTIN
3250613198763
Connection type main circuit
Cable clamp
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
Yes
Designed as a safety switch
No
Designed as a maintenance/repair switch
Yes
Version as reversing switch
No
Design of the actuating element
Gag
Rated operational power at AC-23, 400 V
508kW
Rated operating voltage
220 to 690 V
Rated continuous current Iu
630A
Rated continuous current at AC-21, 400 V
630A
Rated continuous current at AC-23, 400 V
500A
Rated short-time withstand current Icw
7.6kA
Color of the actuator
Gray
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
Yes
Suitable for intermediate construction
No
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
690V
Motor drive integrated
No
Motor drive optional
Yes
Number of poles
4
Protection class (IP), front
IP40
Protection class (NEMA)
Other
Voltage release optional
Yes
Lockable
Yes
No reviews yet — your comment may be first.