Load changeover switch 4-pole 63A. Changeover switch according to DIN EN 60947-3 for switching under load between two low-voltage circuits with safety separation. For mounting on DIN rail or mounting plate. Three switching positions I - 0 - II.
Property | Value |
Number of poles: | 4 |
Rated operating power at AC-23, 400 V: | 28 kW |
Rated continuous current Iu: | 63 A |
Max. Rated operating voltage Ue at AC: | 690 V |
Design as EMERGENCY STOP device: | no |
Protection class (IP), front: | IP20 |
Connection type main circuit: | Screw connection |
Device design: | Built-in device, fixed installation technology |
Design of the actuating element: | short rotary handle |
Suitable for floor mounting: | yes |
Conditional Rated short-circuit current Iq: | 100 kA |
Integrated motor drive: | no |
Suitable for 4-hole front mounting: | no |
Version as maintenance/repair switch: | yes |
Voltage release optional: | no |
Suitable for central front mounting: | no |
Suitable for intermediate installation: | no |
Suitable for Distribution board installation: | yes |
Version as main switch: | yes |
Version as safety switch: | yes |
Motor drive optional: | no |
Lockable: | yes |
Version as reversing switch: | yes |
Rated short-time withstand current Icw: | 2.5 kA |
Color of the actuating element: | black |
Rated operating voltage: | 380 to 690 V |
Switching capacity at 400 V: | 41 kW |
Rated continuous current at AC-21, 400 V: | 63 A |
Number of switches: | 1 |
Rated continuous current at AC-23, 400 V: | 63 A |
Protection class (NEMA): | other |
Features
Manufacturer
HAN
HI403R
GTIN
3250613190064
Connection type main circuit
Screw connection
Number of switches
1
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
No
Designed as a safety switch
Yes
Designed as a maintenance/repair switch
Yes
Version as reversing switch
Yes
Design of the actuating element
Short twist grip
Conditional rated short-circuit current Iq
100kA
Rated operational power at AC-23, 400 V
28kW
Rated operating voltage
380 to 690 V
Rated continuous current Iu
63 A
Rated continuous current at AC-21, 400 V
63 A
Rated continuous current at AC-23, 400 V
63 A
Rated short-time withstand current Icw
2.5kA
Color of the actuator
Black
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
No
Suitable for distribution board installation
Yes
Suitable for intermediate construction
No
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
690V
Motor drive integrated
No
Motor drive optional
No
Number of poles
4
Switching capacity at 400 V
41kW
Protection class (IP), front
IP20
Protection class (NEMA)
Other
Voltage release optional
No
Lockable
Yes
No reviews yet — your comment may be first.