Automatic load changeover switch with switch position indicator 4P 100A 400V. Modular automatic load changeover switch with switch position indicator in accordance with IEC 60947-3 and IEC 60947-6-1 switches between source 1 (e.g. mains voltage) and source 2 (e.g. emergency power supply). In the event of a power failure, an integrated control system takes over the emergency power supply and when the power returns, the device switches back automatically. The DIN rail device with built-in padlock function is self-supplied via the feed-in. Measurement accuracy: frequency 1%, voltage 1%. Protection class: Class 1. Configuration is carried out using 4 potentiometers and DIP switches on the front of the device. Changeover switches ensure: - Stable positions (I - 0 - II), no impairment due to typical vibrations and shocks - Simple installation with effective ergonomics - Window with position indicator I - 0 - II - Integrated switch shutdown. Note: To accommodate up to 2 auxiliary contact blocks and 1 NOC auxiliary contact (for each position I -0 - II).
Feature | Value |
Number of poles: | 4 |
Rated operational power at AC-23, 400 V: | 45 kW |
Rated continuous current Iu: | 100 A |
Max. Rated operating voltage Ue at AC: | 415 V |
Design as EMERGENCY STOP device: | no |
Protection class (IP), front: | IP20 |
Connection type main circuit: | Screw connection |
Device design: | Built-in device, fixed installation technology |
Design of the actuating element: | other |
Suitable for floor mounting: | yes |
Conditional Rated short-circuit current Iq: | 50 kA |
Motor drive integrated: | yes |
Suitable for front mounting 4-hole: | no |
Version as maintenance/repair switch: | yes |
Voltage release optional: | no |
Suitable for front mounting central: | no |
Suitable for intermediate installation: | no |
Suitable for Distribution board installation: | yes |
Version as main switch: | yes |
Version as safety switch: | yes |
Motor drive optional: | no |
Lockable: | yes |
Version as reversing switch: | yes |
Rated short-time withstand current Icw: | 7 kA |
Color of the actuating element: | other |
Rated operating voltage: | 380 to 415 V |
Switching capacity at 400 V: | 65 kW |
Rated continuous current at AC-21, 400 V: | 100 A |
Number of switches: | 1 |
Rated continuous current at AC-23, 400 V: | 100 A |
Protection class (NEMA): | other |