Miniature circuit breaker 1-pole 6kA B characteristic 16A 1 module
Miniature circuit breaker in accordance with DIN0641 part 11/8.92, contact protection IP2x in accordance with DIN0106 part
100 with symbol. LS with time-delayed thermal release for overload protection and
electromagnetic release for short-circuit protection. Suitable for the subsequent installation of
additional devices. Labelling option directly on the device and individual removal from the
phase rail assembly by unlocking the quick-release top hat rail fastening.
Technical features
Rated operating voltage Ue 230/400 V
Rated current 16 A
Trigger characteristic B
Rated breaking capacity 6 kA
Number of poles 1 P
Insulation voltage 500 V
Number of modules 1
Frequency 50/60 Hz
Connection type screw technology
Torque 2.8Nm
Total power loss under rated current 2.44 W
Device service life, electrical switching cycles 4000
Device service life, mechanical switching cycles 20000
Property | Value |
B | |
Rated current: | 16 A |
Rated voltage: | 400 V |
Voltage type: | AC |
Frequency: | 50 to 60 Hz |
Width in pitch units: | 1 |
Number of poles (total): | 1 |
Energy limitation class: | 3 |
Additional equipment possible: | no |
Overvoltage category: | 3 |
Installation depth: | 70 mm |
Protection class (IP): | IP20 |
Rated switching capacity Icn according to EN 60898 at 230 V: | 6 kA |
Rated switching capacity Icu according to IEC 60947-2 at 230 V: | 6 kA |
Pollution level: | 2 |
Switching neutral conductor: | no |
Number of protected poles: | 1 |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Ambient temperature during operation: | -25 to 70 °C |
Connectable conductor cross-section, stranded: | 1 to 25 mm² |
Connectable conductor cross-section, single-wire: | 1 to 35 mm² |