Description
Features
Reviews
Miniature circuit breaker 3-pole 6kA B characteristic 10A 3 modules. Miniature circuit breaker according to DIN0641 part 11/8.92, contact protection IP2x according to DIN0106 part 100 with symbol. LS with time-delayed thermal release for overload protection and electromagnetic release for short-circuit protection. Suitable for the subsequent installation of additional equipment. Labeling option directly on the device and individual removal from the phase rail assembly by unlocking the quick-release top-hat rail fastening.
Property | Value |
Tripping characteristic: | B |
Rated current: | 10 A |
Rated voltage: | 400 V |
Voltage type: | AC |
Frequency: | 50 to 60 Hz |
Width in pitch units: | 3 |
Number of poles (total): | 3 |
Energy limitation class: | 3 |
Additional equipment possible: | yes |
Overvoltage category: | 3 |
Installation depth: | 70 mm |
Protection class (IP): | IP20 |
Rated switching capacity Icu according to IEC 60947-2 at 400 V: | 10 kA |
Rated switching capacity Icn according to EN 60898 at 400 V: | 6 kA |
Pollution level: | 2 |
Switching neutral conductor: | no |
Number of protected poles: | 3 |
Rated insulation voltage Ui: | 500 V |
Rated impulse withstand voltage Uimp: | 4 kV |
Ambient temperature during operation: | -25 to 70 °C |
Connectable conductor cross-section, stranded: | 1 to 25 mm² |
Connectable conductor cross-section, solid: | 1 up to 35 mm² |
Features
Manufacturer
HAN
MBN310
GTIN
3250614310386
Connectable conductor cross-section solid
1 to 35 mm²
Connectable conductor cross-section stranded
1 to 25 mm²
Number of protected poles
3
Trigger characteristics
B
Rated insulation voltage Ui
500V
Rated switching capacity Icn according to EN 60898 at 400 V
6kA
Rated switching capacity Icu according to IEC 60947-2 at 400 V
10kA
Rated voltage
400V
Rated impulse withstand voltage Uimp
4kV
Rated current
10A
Width in pitch units
3
Installation depth
70 mm
Energy limitation class
3
Frequency
50 to 60 Hz
Switching neutral conductor
No
Number of poles (total)
3
IP protection)
IP20
Voltage type
AC
Ambient temperature during operation
-25 to 70 °C
Degree of contamination
2
Additional equipment possible
Yes
Overvoltage category
3
No reviews yet — your comment may be first.